# Free SOT-001 practice questions

> 10 free SOT-001 practice questions with the correct answer and an explanation.

Page: https://devopscodelab.com/exams/comptia-sot-001/free-practice-questions/
Practice exams: https://devopscodelab.com/exams/comptia-sot-001/

### Question 1 of 10

A system integrator must connect controllers from several vendors to a plant-wide information platform. The requirements include platform independence, a rich information model, and built-in options for message signing, encryption and certificate-based application authentication. Which protocol BEST meets these requirements?

- A. OPC UA (IEC 62541)
- B. DNP3 over serial
- C. Modbus TCP
- D. EtherNet/IP with CIP

**Answer:** A

**Explanation:** OPC UA is a platform-independent standard with an extensible information model and a security model that supports signing, encryption and X.509 application certificates. Modbus TCP lacks native security and a rich information model. EtherNet/IP is widely used but its security extension (CIP Security) is not the vendor-neutral information-modeling platform described, and DNP3 over serial is a utility telemetry protocol that does not provide the requested information model.

### Question 2 of 10

A plant's process hazard analysis (PHA) identified that overpressure in a vessel could cause a release. The OT security team wants to include cyber-initiated causes, such as manipulated setpoints or disabled alarms, in the same structured study. Which approach does this describe?

- A. Running a quantitative penetration test against the vessel's pressure transmitter in production
- B. Replacing the PHA with an annualized loss expectancy calculation for each process vessel
- C. Extending HAZOP or PHA methods into a cyber PHA that treats cyberattacks as initiating causes
- D. Creating a separate IT risk register that excludes physical consequences from cyber events

**Answer:** C

**Explanation:** A cyber PHA, sometimes called a cyber HAZOP, extends established process safety methods so cyber-initiated deviations are analyzed alongside other causes, linking cyber risk to physical consequences. ALE calculations do not analyze process deviations, penetration testing production instruments risks the process, and an IT-only register that excludes physical consequences misses the very impacts the team wants to study.

### Question 3 of 10

A critical infrastructure operator wants to start its risk work by identifying the few functions whose failure would be catastrophic, assume a capable adversary already has access, and then engineer out the paths that lead to those consequences. Which methodology is this?

- A. Consequence-driven, cyber-informed engineering
- B. Vulnerability-centric patch prioritization
- C. Qualitative likelihood heat mapping
- D. Annual compliance gap assessment

**Answer:** A

**Explanation:** Consequence-driven, cyber-informed engineering (CCE), developed at Idaho National Laboratory, starts from high-consequence events, assumes compromise and uses engineering changes to remove or limit pathways. A compliance gap assessment measures conformance, vulnerability-centric patching starts from weaknesses rather than consequences, and heat mapping ranks risks without engineering consequence elimination.

### Question 4 of 10 (choose 2)

A US water utility wants to both receive and contribute threat information with peers and government. Which two channels are designed for this? (Choose two.)

- A. Subscribing to a vendor's product newsletter
- B. Filing a regulatory compliance self-report
- C. Joining the sector's ISAC, such as WaterISAC
- D. Posting details on a public industry forum
- E. Participating in CISA's Automated Indicator Sharing

**Answer:** C, E

**Explanation:** Sector ISACs and CISA's Automated Indicator Sharing program provide trusted, two-way channels to exchange threat information. A vendor newsletter only delivers product news one way, a compliance self-report addresses regulatory violations rather than threat sharing, and a public forum lacks trust and handling controls and may expose sensitive details.

### Question 5 of 10

A utility wants access to substation relay settings to be granted only when the user is a protection engineer, the request comes from a utility-managed laptop, and the time falls within an approved maintenance window. Which access control model BEST supports these combined conditions?

- A. Attribute-based access control
- B. Rule-based access control by IP
- C. Discretionary access control
- D. Role-based access control

**Answer:** A

**Explanation:** Attribute-based access control evaluates multiple attributes of the user, device and environment, such as job function, device management state and time window, in a single policy decision. RBAC alone considers only role, DAC relies on owner-granted permissions, and IP-based rules cannot express user role or device posture.

### Question 6 of 10

A protection engineer argues that encrypting GOOSE messages between relays would add latency the protection scheme cannot tolerate. The security architect still wants to prevent spoofed messages. Which approach BEST balances these needs?

- A. Use message authentication to ensure integrity and origin without full encryption
- B. Route GOOSE messages through the enterprise firewall for inspection
- C. Accept spoofing risk because time-critical traffic cannot be protected in any way
- D. Encrypt all GOOSE traffic regardless of the latency impact on protection

**Answer:** A

**Explanation:** Authentication with message authentication codes protects integrity and origin with lower overhead than full encryption, addressing spoofing while respecting timing constraints, as in IEC 62351 approaches. Forcing encryption ignores protection timing, accepting the risk ignores available controls, and routing through an enterprise firewall adds latency and breaks substation design.

### Question 7 of 10

An OT SOC has limited storage. It wants to support investigations of activity that may have started months earlier. Which retention strategy BEST balances cost and investigative value?

- A. Keep full captures briefly and flow and protocol metadata much longer
- B. Keep only firewall deny logs because allowed traffic is assumed to be legitimate
- C. Keep no network data and rely only on operator shift logs for investigations
- D. Keep full packet captures for a year and discard all metadata after one week

**Answer:** A

**Explanation:** Full packet capture is storage-intensive, so a short window combined with long retention of flow and protocol metadata supports investigations of long dwell times at reasonable cost. A year of full PCAP without metadata is costly and less searchable, deny-only logs miss activity that was allowed, and shift logs are not a substitute for network evidence.

### Question 8 of 10

A new vulnerability with a CVSS base score of 9.8 affects an HMI web service. The HMI is in an isolated zone with no web service exposed and no known exploitation. A medium-severity vulnerability on an internet-reachable remote access gateway is listed in CISA's Known Exploited Vulnerabilities catalog. Which should be prioritized first?

- A. Both equally, because severity scores already include asset exposure
- B. The HMI, because its CVSS base score is the highest of the two findings
- C. The remote access gateway, because it is exposed and actively exploited
- D. Neither, because OT systems should never be patched outside outages

**Answer:** C

**Explanation:** Prioritization should weigh exposure and exploitability, and an internet-facing gateway with known exploitation poses a more immediate risk than an unreachable service with a higher base score. CVSS base scores do not account for an organization's specific exposure, and OT systems still need risk-based remediation, sometimes with compensating controls.

### Question 9 of 10 (choose 2)

After an incident, a manufacturer prepares its lessons-learned output. Which two items should be included? (Choose two.)

- A. Raw packet captures from the entire incident period
- B. Assigned owners and deadlines for corrective actions
- C. A recommendation to cancel the IR retainer to save cost
- D. Updates to playbooks based on what did and did not work
- E. Individual performance ratings for each responder

**Answer:** B, D

**Explanation:** Effective lessons learned update procedures and assign corrective actions with owners and deadlines. Raw packet captures belong in the evidence repository rather than the lessons-learned output, performance ratings turn the review into blame and discourage reporting, and cancelling the retainer reduces future readiness.

### Question 10 of 10

A regional utility adopts a framework that applies the Incident Command System, with an incident commander, defined sections and span-of-control rules, specifically to industrial cyber incidents. Which framework is this?

- A. MITRE ATT&CK for ICS
- B. ISO/IEC 27035
- C. NIST CSF 2.0
- D. ICS4ICS

**Answer:** D

**Explanation:** ICS4ICS adapts the Incident Command System used by emergency responders to industrial control system cyber incidents. NIST CSF 2.0 is a cybersecurity outcomes framework, ISO/IEC 27035 is a general incident management standard, and ATT&CK for ICS catalogs adversary techniques.

Ready for a timed run? Take the free 15-question SOT-001 mini exam: https://devopscodelab.com/app/exams/comptia-sot-001/mini/

DevOpsCode Lab is not affiliated with CompTIA. SOT-001 and related names are trademarks of their owners. We write every question ourselves; these are not real exam questions.